Voltage - Scenario 2

Below is a modified version of Example D15 (Voltage Drop Calculation) in Appendix D of the 2017 Philippine Electrical Code (PEC). This post is a single-phase version of the three-phase example in the previous scenario . The same methods in understanding schematics and applying Kirchhoff's Laws are used, with minor adjustments in the loop diagrams and voltage calculations. SITUATION A single-phase transformer supplies 230 Volts to a structure via two 250 mm^2 THWN copper conductors in steel conduit 15.2 meters long, where the main service panel draws a total of 295 Amperes. One of the circuits in the main service panel feeds a single-phase motor via two 5.5 mm^2 THWN copper conductors in steel conduit 30.5 meters long. This electric motor is rated 60 Hertz, 230 Volts, and draws a full load current of 20 Amperes at 80% power factor. How much voltage drops are felt at the main service panel and at the motor terminals, coming from the transformer? ANALYSIS 1.) ONE-LI...