Posts

Showing posts with the label sizing

https://www.vultr.com

The Everywhere Cloud

Deploy an instance.
Accelerate your application.


Faults - Scenario 9

Image
Below is a modified version of Example D14 (Simplified Fault Current Calculation) in Appendix D of the 2017 Philippine Electrical Code (PEC). This post presents a single-phase system, without any motors present in the adjacent circuits, tapping into the three-phase source. This serves as a comparison to the previous scenario where a three-phase system taps into the three-phase source. The goal here is to examine what magnitudes are to be expected in single-phase circuits compared to three-phase circuits, and how these magnitudes factor into the selection of protective device ratings. SITUATION An industrial complex receives 230 V, 60 Hz from a single-phase distribution transformer rated 300 kVA and an impedance of 5%. The transformer taps into a three-phase 34.5 kV supply with a 1,000 MVA short-circuit capacity. Using the per-unit method, what maximum symmetrical fault currents may occur in each of the fault points "a", "b", and "c"? From the...

Faults - Scenario 8

Image
Below is a modified version of Example D14 (Simplified Fault Current Calculation) in Appendix D of the 2017 Philippine Electrical Code (PEC). This post is a single-phase version of the three-phase example in the previous scenario  without any motors present in the adjacent circuits. The goal here is to examine what magnitudes are to be expected in single-phase circuits compared to three-phase circuits, and how these magnitudes factor into the selection of protective device ratings. SITUATION An industrial complex receives 230 V, 60 Hz from a single-phase distribution transformer rated 300 kVA and an impedance of 5%. The transformer taps into a single-phase 34.5 kV supply with a 1,000 MVA short-circuit capacity. Using the per-unit method, what maximum symmetrical fault currents may occur in each of the fault points "a", "b", and "c"? From these fault currents, what are the minimum symmetrical kiloAmpere Interrupting Capacity (kAIC) ratings needed fo...

Faults - Scenario 7

Image
Below is a modified version of Example D14 (Simplified Fault Current Calculation) in Appendix D of the 2017 Philippine Electrical Code (PEC). This post is almost identical to the previous scenario , except that there are no motors present in the adjacent circuits. SITUATION An industrial complex receives 230 V, 60 Hz from a bank of three single-phase distribution transformers interconnected into a three-phase configuration. Each distribution transformer is rated 100 kVA, and the entire bank has an impedance of 5%. The transformer bank taps into a 34.5 kV supply with a 1,000 MVA short-circuit capacity. Using the per-unit method, what maximum symmetrical fault currents may occur in each of the fault points "a", "b", and "c"? From these fault currents, what are the minimum symmetrical kiloAmpere Interrupting Capacity (kAIC) ratings needed for each molded case circuit breaker (MCCB) A, B, and C? ANALYSIS 1.) ESTABLISH COMMON BASE VALUES. ...

Electrical DEAN for Mobile Devices

Image
Get it on  Huawei AppGallery now! (Keyword: "ElectricalDEAN") ========== Electrical DEAN for Mobile Devices is an electrical design analysis app based on the Philippine Electrical Code, the SI Modernized Metric System, and equivalent provisions from the National Electrical Code (NFPA 70). Electrical design analysis is primarily about detailed calculations of wire gauges, conduit sizes, protective device ratings, fault currents, voltage drops and other technical matters necessary for the safe and proper operation of electrical systems. The Electrical DEAN mobile app is intended as an educational tool for those who are new in the electrical trade, and as a research tool for veterans who need quick calculations to compare with their own electrical designs. Currently, it covers the fundamentals of electrical design analysis: conductor and conduit data, fault currents and voltage drops (1-phase and 3-phase), and general-purpose circuit sizing (circui...

Standards - Scenario 2

Image
This post is inspired by the 2017 Philippine Electrical Code (PEC) Appendix D Example D12 (Voltage Regulators, Three-Phase). SITUATION A three-phase automatic voltage regulator (AVR) rated 30 kVA, 60 Hertz, 350-530 Volts input, 230 Volts output needs a feeder circuit from the main service panel. The AVR is installed in an air-conditioned data center with raised floors, and the conduit for electric conductors shall be run underneath. The wires to be used are made of copper conductors, with insulation rated for 75 degC operating temperature and of type THW (Thermoplastic, Heat-resistant, for Wet location). The raceway for the circuit is a rigid PVC Schedule 80 conduit. What size of 3ph circuit breaker, wires, and raceway are needed? ANALYSIS 1.) ONE-LINE DIAGRAM              i,avr,1L ---> o|---V,msp,LN---V,avr,LN---|> 2.) CIRCUIT CALCULATIONS 2.1.) Kirchhoff's Voltage Law, LN: -V,msp,LN + V,avr,LN = 0 V,avr,LN = V,msp,LN 2...

Standards - Scenario 1

Image
This post is inspired by the 2017 Philippine Electrical Code (PEC) Appendix D Example D11 (Voltage Regulators, Single-Phase). SITUATION A single-phase automatic voltage regulator (AVR) rated 5 kVA, 60 Hertz, 165-280 Volts input, 230 Volts output needs a feeder circuit from the main service panel. The AVR is installed in an air-conditioned data center with raised floors, and the conduit for electric conductors shall be run underneath. The wires to be used are made of copper conductors, with insulation rated for 75 degC operating temperature and of type THW (Thermoplastic, Heat-resistant, for Wet location). The raceway for the circuit is a rigid PVC Schedule 80 conduit. What size of 1ph circuit breaker, wires, and raceway are needed? ANALYSIS 1.) ONE-LINE DIAGRAM i,avr,1ph ---> o|---V,msp,1ph---V,avr,1ph---|> 2.) CIRCUIT CALCULATIONS 2.1.) Kirchhoff's Voltage Law, 1ph: -V,msp,1ph + V,avr,1ph = 0 V,avr,1ph = V,msp,1ph 2.2.) Power equation, ...

Standards - Note 4

Image
RACEWAY SIZES (CONDUIT AND TUBING) 1.) Raceway Sizing There are three options for sizing raceways according to 2017 PEC Table 10.1.1.1 [ or 2017 NEC Chapter 9 Table 1 ], based on cross-sectional areas: A.) 53% raceway area for 1 conductor (a multiconductor cable is treated as a single conductor [Note 9]) B.) 31% raceway area for 2 conductors C.) 40% raceway area for over 2 conductors 1.1.) Choosing Between Alternatives For future expansion purposes, option (A) is far from practical. This may have use in very specific installations that are assumed to be not needing any expansions, but upgrades will definitely happen and option (A) will eventually become a bottleneck. Option (B) for 2 conductors having a smaller area than either option (A) for 1 conductor or option (C) for over 2 conductors may seem nonsensical, but it actually does make sense. Having 2 conductors usually means 2 live wires supplying loads that may require an equipment grounding conductor ...

Standards - Note 3

Image
WIRE AMPACITIES, INSULATORS, AND IMPEDANCES Below are some useful tables pertaining to ampacities, insulators, and impedances of various wires. These are derived from the 2017 Philippine Electrical Code [ or the 2017 National Electrical Code ], but are rearranged in a manner that is easier to interpret and understand. 1.) Allowable Ampacities of Insulated Conductors in Raceway. The areas, ampacities, and insulation types of the following tables are based on 2017 PEC Table 3.10.2.6(B)(16) [ or 2017 NEC Table 310.15(B)(16) ]. 1.1.) Copper Wire Ampacities --------------------------------------- |  Copper  |  Insulation Max Op. Temp | --------------------------------------- |   Area   | 60degC | 75degC | 90degC | |   mm^2   |  Amps  |  Amps  |  Amps  | --------------------------------------- |    2.0   |    15  |    20  |    25  ...

Faults - Scenario 6

Image
Below is a modified version of Example D14 (Simplified Fault Current Calculation) in Appendix D of the 2017 Philippine Electrical Code (PEC). This post is almost identical to the previous scenario , except that this time, an alternative common base value is used. The goal here is to show that regardless of the common base values utilized and the new per-unit values computed, the actual values remain practically the same. SITUATION An industrial complex receives 230 V, 60 Hz from a bank of three single-phase distribution transformers interconnected into a three-phase configuration. Each distribution transformer is rated 100 kVA, and the entire bank has an impedance of 5%. The transformer bank taps into a 34.5 kV supply with a 1,000 MVA short-circuit capacity. Using the per-unit method, what maximum symmetrical fault currents may occur in each of the fault points "a", "b", and "c"? From these fault currents, what are the minimum symmetrical kiloAmper...